GTACSR/ GZTACSR: (Galvanized Twist Aluminum Conductor Steel Reinforced)
These conductors have a special construction feature with a small gap filled with grease between the high strength steel core and the thermal resistant Al-Zr alloy conductive layers. Installation method of GZTACSR is well but requires skilled specialists because at the time of sagging, a special sagging method is required to apply all the tension to the steel core only. Gap-type conductors are particularly suitable to replace ACSR conductors in flat lands or in any case with small difference in level.
Key Features of GTACSR/ GZTACSR:
- Tension the core and the external layer independently to have the kneepoint at the installation temperature
- Limiting the sag increase with the increase of the temperature by the thermal expansion coefficient above knee-point related to the steel core
- Maintaining the mechanical strength of the conductor with continuous operating temperature up to 150°C & 210°C
- Reduced cost due to no expensive materials being required
The above design is only a sample of the options available, for reference purposes only. Our policy of continuous improvement may result in a change of specifications without notice. If any discrepancies might be between the data sheet values and standards, we reserve the rights to make technical changes. Our company will not be held responsible, as all or any of pictures, drawings, weights and dimensions details or other elements in this document are only indicative and must not be considered contractual. Contact our sales team for other specifications or custom made products.